You Are Here: Home>>Product Center>>Current Limiting Protector
Introduction
The JGXL-63S three-phase four-wire current-limiting overvoltage and underVoltage Protector is mainly used in power systems with AC 50Hz (60Hz), a rated working voltage of 220/380V, a main body rated current from 2A to 63A, an adjustable working current of the intelligent controller from 2A to 63A, and a control power from .5KW to 20KW, to make, carry and break currents or voltages under normal conditions (including specified overload conditions), and can also make, carry for a certain period of time and break currents or voltages under specified abnormal conditions (such as short circuit, undervoltage, etc.).
The three-phase four-wire current-limiting overvoltage and underVoltage Protector adopts a modular product structure, featuring advantages such as compact size, high reliability, and ease of operation. The main functions of the product include: overvoltage, undervoltage, phase loss, neutral line break, overcurrent, instantaneous short circuit, three-phase imbalance, undercurrent, phase sequence, RS485 communication, one-key restore to factory settings, etc. It is widely used in power distribution and motor protection control systems in fields such as telecommunications, metallurgy, coal mining, steel, petrochemicals, ports, ships, railways, hospitals, and intelligent buildings.
Main Technical Parameters
1. Voltage detection range: AC80~450V, accuracy class: Class 1.0.
2. Current detection range: 1~63A, accuracy class: Class 1.0.
3. Product power consumption: ≤2W.
4. Short-circuit current withstand: 2000A.
5. Mechanical life ≥ 100,000 operations, electrical life 5,000 operations.
6. Product wiring method: bottom-in top-out, top-in bottom-out. The default wiring method is bottom-in top-out.
7. Wiring capacity: 16 mm².

Overall Dimensions


Keywords: Three-phase four-wire self-recovery overvoltage and underVoltage Protector, three-phase four-wire current-limiting protector, phase sequence protector, phase loss protector, neutral loss protector, current-limiting protector, phase loss neutral loss phase sequence overload short circuit three-phase imbalance undercurrent three-phase four-wire current-limiting overvoltage and underVoltage Protector
Product: Three-Phase Four-Wire Current-Limiting Over/under Voltage Protector|phase Loss, Three-Phase Imbalance, Neutral Line Break, Phase Sequence Protector|jgxl-63
Overview: The JGXL-63S three-phase four-wire current-limiting overvoltage and underVoltage Protector is mainly used to make, carry, and break current or voltage under normal conditions (including specified overload conditions) in power systems with AC 50Hz (60Hz), a rated working voltage of 220/380V, a main body rated current from 2A to 63A, an adjustable operating current of the smart controller from 2A to 63A, and a control power from 0.5KW to 20KW. It can also make, carry for a certain period, and break current or voltage under specified abnormal conditions (such as short circuit, undervoltage, etc.). The current-limiting three-phase four-wire overvoltage and underVoltage Protector adopts a modular product structure, featuring the advantages of compact size, high reliability, and easy operation. The main functions of the product include: overvoltage, undervoltage, phase loss, neutral line loss, overcurrent, instantaneous short circuit, three-phase imbalance, undercurrent, phase sequence, RS485 communication, one-key factory reset, and other functions.
| Brand | ELEJG / Wenzhou Jiangguang Electric Technology Co., Ltd. |
|---|---|
| Model | Three-Phase Four-Wire Current-Limiting Over/under Voltage Protector|phase Loss, Three-Phase Imbalance, Neutral Line Break, Phase Sequence Protector|jgxl-63 |
| Technical Docs | View / Download Manual |
| Inquiry | Contact Us |
Copyright © 2018-2020 Wenzhou Jiangguang Electrical Technology Co., Ltd. All Rights Reserved. Zhejiang Icp Record No. 15019439-3